Impact load

The load a panel survives when a weight is dropped onto it, simulating dropped tools and equipment during fit-out.

Related terms in Raised floors

Rolling load
The load a panel withstands from a wheel rolling across it (pallet trucks, server racks on castors, MEWPs) for a set number of passes, typically 10 and 10,000.
Uniformly distributed load (UDL)
The load spread evenly over the whole floor area, in kN/m², such as storage, dense furniture or battery rooms.
Ultimate load
The load at which a panel fails in test. Rated loads are set well below it so the floor keeps a wide safety margin.
Deflection
How far a panel bends under load. Load ratings are tied to a maximum permitted deflection, not only to failure.
Concentrated load
The load a panel carries on a small area (a 25 × 25 mm indenter in the CISCA test), like a chair leg or cabinet foot, without exceeding the allowed deflection. Nord Floors grades run from 3.7 to 11.1 kN.
Load grade
The named rating of a panel (for example 4.5 kN) that tells the specifier which concentrated, uniform and rolling loads it carries.
Edge trim
A plastic or metal edge band around a panel that protects the edge, keeps finishes neat and helps panels sit tight in the grid.
Chemical anchoring
Fixing pedestal bases to the slab with a structural adhesive. Suited to lower floor heights.