Perforated floor tile calculator: how many do you need?
Work out how many perforated panels or air grilles your raised floor needs, from your cooling unit (CRAC or CRAH) datasheet, your IT load or your number of racks. We show every step, so you can check it with your mechanical engineer.
1Where shall we start?
Pick what you have in hand. Any of these works; the datasheet is the most accurate.
2Find the airflow on the datasheet
Open the datasheet of your CRAC or CRAH unit (the cooling units that blow cold air under the floor). Look in the technical data table for a line like this:
| Total cooling capacity | 65.2 kW |
| Sensible cooling capacity | 60.1 kW |
| Air flow (nominal) | 18,000 m³/h |
| External static pressure | 20 Pa |
| Fans | 2 × EC |
It may be called: Air flowAirflow rateAir volumeNominal air flowSupply air flowFan air flowAir quantity
Several airflow numbers? Which one do I use?
Use the nominal or rated airflow, the one listed with the cooling capacity you designed for. If the table shows airflow at several external static pressures (ESP), take the one nearest your design (often 20–50 Pa for downflow units). If it shows a fan-speed range, take the speed you will run. Not sure? Send us the datasheet and our engineers read it for you.
CFM, l/s and m³/s are converted for you.
3How many units?
Count every cooling unit serving this floor. Standby units (the spare, often called N+1) don't count towards airflow.
4How well are the floor's openings sealed?
Some cold air always leaks out through cable cut-outs and gaps instead of the panels.
Tip: grommets and brush seals on every cut-out mean fewer panels and better cooling.
5Underfloor air pressure
How hard the cooling units push air under the floor. Your mechanical engineer sets it. Not sure? Keep 12.5 Pa: a common, safe design value.
6Room area (optional)
Only to show how much of the floor the panels take.
Perforated panel, round holes, no damper, 600 × 600 mm.
- Each cooling unit moves 18,000 m³/h.
- 2 of 3 units run (1 on standby), so they supply 36,000 m³/h under the floor.
- About 15% escapes through cable cut-outs and gaps (average floor), leaving 30,600 m³/h for the panels.
- One perforated panel passes about 900 m³/h at 12.5 Pa, so 30,600 ÷ 900 = 34 pieces (rounded up).
Nord Floors finish to match the floor (nHPL, nSDV or nSteelCement to suit). Same grid and load grade family as the solid panels. Airflow per panel is a typical published value for this panel type, for planning; Nord Floors confirms the count, positions and load rating against your mechanical design.
How the calculation works
- Airflow under the floor = airflow of one cooling unit × units running (standby units do not count).
- Airflow reaching the panels = that × (1 − leakage through cut-outs and gaps).
- Airflow per panel rises with underfloor pressure: about 900 m³/h for a perforated panel and 2,930 m³/h for an air grille at 12.5 Pa.
- Pieces = airflow reaching the panels ÷ airflow per panel, rounded up.
No cooling units chosen yet? Start from the heat: airflow (m³/h) ≈ IT load (kW) × 2,982 ÷ temperature rise across the servers (°C).
Worked example
| Cooling units | 3 × 18,000 m³/h, 1 on standby |
|---|---|
| Airflow under the floor | 2 × 18,000 = 36,000 m³/h |
| Leakage (average floor) | 15% → 30,600 m³/h to the panels |
| Underfloor pressure | 12.5 Pa |
| Perforated panels | 30,600 ÷ 900 = 34 pieces |
| Or air grilles | 30,600 ÷ 2,930 = 11 pieces |
Planning values. Nord Floors confirms the count, positions and load rating against your mechanical design.
Perforated panel questions
How many perforated panels or air grilles does a room need?
Multiply one cooling unit's airflow (from its datasheet) by the number of running units, take off the share that leaks through cable cut-outs (about 5% if sealed, 15% typical, 30% unsealed), and divide by the airflow one panel passes at your underfloor pressure. Example: 3 units of 18,000 m³/h with 1 on standby supply 36,000 m³/h; with typical leakage about 30,600 m³/h reaches the panels; a perforated panel passes about 900 m³/h at 12.5 Pa, so you need 34 perforated panels, or 11 air grilles.
Where do I find the airflow on a CRAC or CRAH datasheet?
In the technical data table, on a line called air flow, airflow rate, air volume, nominal air flow or supply air flow, in m³/h, CFM, l/s or m³/s. Use the nominal or rated value at your design external static pressure. If the datasheet only shows cooling capacity, use the sensible cooling in kW: airflow (m³/h) ≈ kW × 2,982 ÷ the air temperature rise (about 11 °C).
What is the difference between a perforated panel and an air grille?
A perforated panel is about 25% open and passes enough air for normal racks; it is finished to match the floor around it. An air grille is about 56% open and passes roughly three times as much air, for dense, high-power racks.
Do I need dampers?
A damper under the panel lets you trim each panel’s airflow to balance the room, but it lowers the panel’s maximum flow. Choose dampers where loads vary across the room or will change over time.
Are perforated panels sold by the square metre?
No. Perforated panels, air grilles and glass vision panels are sold by the piece. They replace solid panels in the same grid and carry the same load grade family.
Where should perforated panels go?
In the cold aisles, in front of the racks’ air intakes. Never in hot aisles or right next to the cooling units, where the air moves too fast and can even be drawn back down.