Find the right raised floor
Nord Floors makes four raised access floor series in Dammam, Saudi Arabia. Pick the panel, then the finish on top, then what the floor carries: we give you the grade, the board layer if one is needed, and the spec clause. We recommend 4.5 kN as the minimum for every office.
Not sure? Most offices use nSteelCement. Pick nGroove only where stone or porcelain must be bonded straight to the panel.
1,200 kg on 4 wheels or feet = 2.94 kN on each.
nSteelCement SC450 · 4.5 kN
Up to 600 mm FFH: no stringers, and chemical (adhesive) anchoring of the pedestals is enough.
SC370 would carry 1.5 kN, but we recommend 4.5 kN as the minimum for every office: a stiffer panel that sounds solid underfoot, stays quieter and lasts longer.
Indicative selection from Nord Floors data sheet values (CISCA A/F test methods). Use categories follow the PSA grades; Nord Floors recommends 4.5 kN minimum for offices and 6.8 kN minimum for MEWP access. Nord Floors engineering confirms the final grade against your equipment schedule.
Airflow panels for underfloor cooling, and glass vision panels to see the cables and services below without lifting a panel. Perforated panels and air grilles replace a few solid panels in the same grid, finished to match the series around them. A 100 m² room typically has only a handful to a few dozen, set by the cooling units' airflow.
Panel lifters lift any panel out of the grid with suction, so the facilities team can reach cables and services without damaging edges or finishes. Every site needs at least one.
Use the double-cup lifter on stone, porcelain and other heavy finishes; press both cups flat before lifting.
The four series side by side
| nSteelCement | nGroove | nHPL | nSDV | |
|---|---|---|---|---|
| Core | Steel cementitious | High-density calcium sulphate | Steel cementitious | Steel cementitious |
| Finish | Carpet, LVT, SPC direct; stone on a board layer | Hard finishes bonded directly | Antistatic HPL, factory-applied | Static dissipative vinyl, factory-applied |
| Thickness | 33 mm | 40 mm | 35 mm | 34.5 mm |
| Finished floor height | 80–2000 mm | 80–2000 mm | 80–2000 mm | 100–2000 mm |
| Load grades | 3.7 to 11.1 kN | 4.5 to 11.1 kN | 3.7 to 11.1 kN | 3.7 to 11.1 kN |
| Fire | A1 | A1, 120-minute integrity to EN 1366-6 | A1 | A1 |
| Acoustic | IIC 58 | IIC 55 | IIC 58 | IIC 58 |
| Pedestal head | cross | round | flat | square |
| Stringers | Above 600 mm FFH | Above 600 mm FFH | Always | Always |
Source: Nordinfini technical data sheets.
Questions consultants ask
Why does Nord Floors recommend 4.5 kN as a minimum?
Lighter grades can carry ordinary office loads, but a 4.5 kN panel is stiffer. It sounds more solid underfoot, transmits less footfall noise and holds up better over the life of the building. We recommend 4.5 kN as the minimum for every office.
Can I put marble or stone on a raised floor?
Yes. nSteelCement is our standard panel and takes marble, stone, porcelain and parquet: fix a plywood, cement board or fibreboard layer to the panels, then lay the finish on it. Carpet tiles, LVT and SPC go straight onto the panel. nGroove is our premium panel for projects that need the hard finish bonded straight to the panel with no board layer.
Can a MEWP or scissor lift be used on a raised access floor?
Yes, on 6.8 kN grades and above. Nord Floors floors at 6.8 kN carry MEWPs on site today. Forklifts and pallet stackers are possible on heavy grades after Nord Floors engineering checks the wheel loads.
When does a raised floor need stringers and mechanical anchoring?
nHPL and nSDV are gravity-laid systems, so they use stringers at every height, from the lowest. nSteelCement and nGroove are corner-locking systems, fixed to the pedestal heads at each corner, so they need stringers only above 600 mm finished floor height. Up to 600 mm, chemical (adhesive) anchoring of the pedestals is enough; above 600 mm, pedestals are mechanically anchored to the slab.
Which standard are Nord Floors raised floors tested to?
Nord Floors follows the CISCA (Ceilings & Interior Systems Construction Association) Recommended Test Procedures for Access Floors for concentrated, ultimate, uniform and rolling loads.
Is woodcore (chipboard) raised flooring suitable for Saudi Arabia?
Usually not the best choice. Woodcore panels have a compressed wood-chip (chipboard) core, made for dry indoor conditions. Coastal humidity in Jeddah and Dammam, water from cleaning or leaks, and wet works during construction can make the core swell and lose strength. Woodcore is combustible (typically Bfl to Dfl fire classes), and many woodcore systems are rated only at light to medium grades. Steel cementitious panels such as nSteelCement are non-combustible (A1), do not swell with moisture, carry 3.7 to 11.1 kN, and last the life of the building; the steel shell is fully recyclable at end of life.
When do I need nHPL or nSDV?
Only where the room needs antistatic (nHPL) or static dissipative (nSDV) flooring, such as data rooms, server rooms and control rooms. Both come with their final finish factory-applied.
How many perforated panels or air grilles does a room need?
Only as many as the cooling needs. They are sold by the piece, not by the square metre. Divide the airflow that reaches the floor (cooling units running, minus leakage) by the airflow one panel passes at the design underfloor pressure. Our perforated panel calculator walks you through it from your CRAC datasheet.
Is Nord Floors raised flooring made in Saudi Arabia?
Yes. All four series are manufactured by Nordinfini in Dammam Industrial Area 2 and supplied across Saudi Arabia and the GCC.