Raised floor selector

Find the right raised floor

Nord Floors makes four raised access floor series in Dammam, Saudi Arabia. Pick the panel, then the finish on top, then what the floor carries: we give you the grade, the board layer if one is needed, and the spec clause. We recommend 4.5 kN as the minimum for every office.

1 · Which raised floor?

Not sure? Most offices use nSteelCement. Pick nGroove only where stone or porcelain must be bonded straight to the panel.

2 · What finish goes on top of nSteelCement?
✓No board layer needed. Carpet tiles, LVT and SPC go straight onto nSteelCement. No board layer needed.
3 · What will the floor carry?
Or enter your heaviest item

1,200 kg on 4 wheels or feet = 2.94 kN on each.

Fine-tune the point load
1.5 kN on one point
Static load
1 kN357912 kN

General offices: the PSA light grade is 1.5 kN, but we recommend 4.5 kN minimum for long-term performance and acoustics.

NSTEELCEMENT GRADES · CONCENTRATED LOAD (kN)
SC370
3.7 kN
SC450
4.5 kN
SC560
5.6 kN
SC680
6.8 kN
SC890
8.9 kN
SC1110
11.1 kN
RecommendedAlso suitableCarries it, below our minimumToo lightRecommended minimum
nSteelCement: 80 to 2000 mm
Recommended

nSteelCement SC450 · 4.5 kN

13.5 kNUltimate
23.3Uniform kN/m²
3.6 kNRolling, 10 passes
3.0 kNRolling, 10,000 passes
300 mmFinished floor height
Not requiredStringers
ChemicalPedestal anchoring
CISCATest standard

Up to 600 mm FFH: no stringers, and chemical (adhesive) anchoring of the pedestals is enough.

SC370 would carry 1.5 kN, but we recommend 4.5 kN as the minimum for every office: a stiffer panel that sounds solid underfoot, stays quieter and lasts longer.

Indicative selection from Nord Floors data sheet values (CISCA A/F test methods). Use categories follow the PSA grades; Nord Floors recommends 4.5 kN minimum for offices and 6.8 kN minimum for MEWP access. Nord Floors engineering confirms the final grade against your equipment schedule.

4 · Special panels (optional) · sold by the piece

Airflow panels for underfloor cooling, and glass vision panels to see the cables and services below without lifting a panel. Perforated panels and air grilles replace a few solid panels in the same grid, finished to match the series around them. A 100 m² room typically has only a handful to a few dozen, set by the cooling units' airflow.

5 · Accessories (optional) · sold by the piece

Panel lifters lift any panel out of the grid with suction, so the facilities team can reach cables and services without damaging edges or finishes. Every site needs at least one.

Use the double-cup lifter on stone, porcelain and other heavy finishes; press both cups flat before lifting.

The four series side by side

nSteelCementnGroovenHPLnSDV
CoreSteel cementitiousHigh-density calcium sulphateSteel cementitiousSteel cementitious
FinishCarpet, LVT, SPC direct; stone on a board layerHard finishes bonded directlyAntistatic HPL, factory-appliedStatic dissipative vinyl, factory-applied
Thickness33 mm40 mm35 mm34.5 mm
Finished floor height80–2000 mm80–2000 mm80–2000 mm100–2000 mm
Load grades3.7 to 11.1 kN4.5 to 11.1 kN3.7 to 11.1 kN3.7 to 11.1 kN
FireA1A1, 120-minute integrity to EN 1366-6A1A1
AcousticIIC 58IIC 55IIC 58IIC 58
Pedestal headcrossroundflatsquare
StringersAbove 600 mm FFHAbove 600 mm FFHAlwaysAlways

Source: Nordinfini technical data sheets.

All about Nord Floors raised access floors →

Questions consultants ask

Why does Nord Floors recommend 4.5 kN as a minimum?

Lighter grades can carry ordinary office loads, but a 4.5 kN panel is stiffer. It sounds more solid underfoot, transmits less footfall noise and holds up better over the life of the building. We recommend 4.5 kN as the minimum for every office.

Can I put marble or stone on a raised floor?

Yes. nSteelCement is our standard panel and takes marble, stone, porcelain and parquet: fix a plywood, cement board or fibreboard layer to the panels, then lay the finish on it. Carpet tiles, LVT and SPC go straight onto the panel. nGroove is our premium panel for projects that need the hard finish bonded straight to the panel with no board layer.

Can a MEWP or scissor lift be used on a raised access floor?

Yes, on 6.8 kN grades and above. Nord Floors floors at 6.8 kN carry MEWPs on site today. Forklifts and pallet stackers are possible on heavy grades after Nord Floors engineering checks the wheel loads.

When does a raised floor need stringers and mechanical anchoring?

nHPL and nSDV are gravity-laid systems, so they use stringers at every height, from the lowest. nSteelCement and nGroove are corner-locking systems, fixed to the pedestal heads at each corner, so they need stringers only above 600 mm finished floor height. Up to 600 mm, chemical (adhesive) anchoring of the pedestals is enough; above 600 mm, pedestals are mechanically anchored to the slab.

Which standard are Nord Floors raised floors tested to?

Nord Floors follows the CISCA (Ceilings & Interior Systems Construction Association) Recommended Test Procedures for Access Floors for concentrated, ultimate, uniform and rolling loads.

Is woodcore (chipboard) raised flooring suitable for Saudi Arabia?

Usually not the best choice. Woodcore panels have a compressed wood-chip (chipboard) core, made for dry indoor conditions. Coastal humidity in Jeddah and Dammam, water from cleaning or leaks, and wet works during construction can make the core swell and lose strength. Woodcore is combustible (typically Bfl to Dfl fire classes), and many woodcore systems are rated only at light to medium grades. Steel cementitious panels such as nSteelCement are non-combustible (A1), do not swell with moisture, carry 3.7 to 11.1 kN, and last the life of the building; the steel shell is fully recyclable at end of life.

When do I need nHPL or nSDV?

Only where the room needs antistatic (nHPL) or static dissipative (nSDV) flooring, such as data rooms, server rooms and control rooms. Both come with their final finish factory-applied.

How many perforated panels or air grilles does a room need?

Only as many as the cooling needs. They are sold by the piece, not by the square metre. Divide the airflow that reaches the floor (cooling units running, minus leakage) by the airflow one panel passes at the design underfloor pressure. Our perforated panel calculator walks you through it from your CRAC datasheet.

Is Nord Floors raised flooring made in Saudi Arabia?

Yes. All four series are manufactured by Nordinfini in Dammam Industrial Area 2 and supplied across Saudi Arabia and the GCC.