Soffit insulation selector

Choose soffit insulation by U-value

Set the U-value your soffit needs and see how thick each board must be. Kingspan Kooltherm K10 phenolic reaches it with the thinnest board and a clean white finish; stone wool and glass wool are here when the fire strategy needs them.

1Where is the soffit?

2What matters most?

Pick one or more.

3U-value target

The U-value of the whole soffit: 200 mm concrete slab plus the board. Lower is better. Take your target from the project energy report; SBC 601 sets a maximum for floors.

U 0.41W/m²K
0.600.15 (best)
Thickness each board needs
Phenolic soffit board ★50 mm
Stone wool soffit slab75 mm
Stone wool fire slab, high density75 mm
Glass wool board100 mm
★ Phenolic needs 50 mm. That is up to 50 mm thinner than the mineral wool options: more headroom under the slab, and less board to lift and fix.
U-values with Kingspan K10
40 mm → U 0.4550 mm → U 0.3660 mm → U 0.3070 mm → U 0.2680 mm → U 0.2390 mm → U 0.21100 mm → U 0.19110 mm → U 0.17120 mm → U 0.16

Calculated to the simple ISO 6946 method: surface resistances 0.17 + 0.04 m²K/W, 200 mm reinforced concrete at 2.3 W/m·K, each board at its stated conductivity, no fixing correction. Kingspan and Nordinfini confirm the final U-value with a project calculation.

4Choose the board

Alternatives: mineral wool
Thickness
Facing
Area
m²

Questions

How thick should soffit insulation be?

It depends on the U-value you need. With a 200 mm concrete slab, Kingspan Kooltherm K10 gives about U 0.36 W/m²K at 50 mm, 0.30 at 60 mm, 0.23 at 80 mm and 0.19 at 100 mm. SBC 601 caps floors at U 0.41. Final U-value by project calculation.

Why is phenolic thinner than mineral wool?

Kooltherm K10 has a thermal conductivity of 0.020 W/m·K (45 mm and thicker), against about 0.033 to 0.038 for stone wool and glass wool. For the same U-value the phenolic board is roughly 40% thinner, which saves headroom in car parks and under podiums.

Is phenolic insulation non-combustible?

No. Phenolic is not an A1/A2 non-combustible product. Many soffits do not need one, so check what the project fire strategy actually requires. Where it insists on non-combustible, the selector shows stone wool alternatives.

How is the U-value calculated?

With the simple ISO 6946 method: surface resistances of 0.17 and 0.04 m²K/W, 200 mm reinforced concrete at 2.3 W/m·K, and the board at its declared conductivity, before any fixing correction. Kingspan and Nordinfini confirm the final figure with a project calculation.

All about Kingspan K10 soffit insulation →