Nord Floors · Antistatic high pressure laminate raised access floor

nHPL Series

nHPL is a steel cementitious raised access floor panel with a factory-applied antistatic high pressure laminate, made in Dammam. It is for server rooms, data centers and command centers where antistatic flooring is required, with loads from 3.7 to 11.1 kN.

600 × 600 mm35 mmFFH 80–2000 mmA1Antistatic HPL

Overview

The same steel cementitious panel as nSteelCement, finished in the factory with antistatic HPL. It is a gravity-laid system on stringers, so any panel lifts out for access to cables and cooling, and drops back into an exact grid.

Use it only where the room needs antistatic flooring. For general offices, use nSteelCement with carpet or LVT.

Features

  • Antistatic HPL finish already on the panel.
  • Always on stringers for a rigid, gravity-laid grid.
  • Same load range as nSteelCement.
  • Perforated panels and grilles finished to match.
nHPL panel on four pedestals with flat heads

Illustration. Flat head pedestals.

Raised access floor panels being laid in an office overlooking Riyadh

Being installed. Panels being laid on pedestals and stringers, with cable trays in the void. Illustration.

Specification

Panel size600 × 600 mm
Thickness35 mm
Weightapprox. 13–20 kg
FinishAntistatic high pressure laminate
Finished floor height80–2000 mm
Squareness0.75 mm max
Flatnessdiagonal 1.0 mm, edge 0.6 mm
Twist1.0 mm
FireNon-combustible, Class A (ASTM E84), A1 (EN 13501)
AcousticIIC 58
PedestalFlat head, galvanised steel

Finishes

Factory-applied antistatic high pressure laminate. No site finish needed.

Understructure

Gravity-laid panels on stringers at every height, from the lowest finished floor heights. Chemical anchoring up to 600 mm FFH; mechanical above.

Applications

Server roomsData centersCommand centersTraining centers

nHPL load grades

GradeConcentratedImpactUltimateUniformRolling, 10 passesRolling, 10,000 passes
HPL3703.7 kN0.6710.8 kN19.8 kN/م²3.0 kN2.2 kN
HPL4504.5 kN0.6713.5 kN23.3 kN/م²3.6 kN3.0 kN
HPL5605.6 kN0.6716.8 kN33.1 kN/م²4.5 kN3.6 kN
HPL6806.8 kN0.6720.1 kN42.6 kN/م²5.6 kN4.5 kN
HPL8908.9 kN0.6726.7 kN49.9 kN/م²6.7 kN5.6 kN
HPL111011.1 kN0.6733.3 kN58.3 kN/م²8.9 kN6.7 kN

Recommended minimum for offices: the 450 grade (4.5 kN). For MEWP access: 680 (6.8 kN) and above. Tested to CISCA Recommended Test Procedures for Access Floors.

Documents

The nHPL data sheet is in Downloads. Ask for the rest with your quotation or submittal pack.

nHPL · Technical data sheet nHPL · Load test report nHPL · Installation guide nHPL · Perforated panel data nHPL · CAD / BIM

Questions about nHPL

Why does Nord Floors recommend 4.5 kN as a minimum?

Lighter grades can carry ordinary office loads, but a 4.5 kN panel is stiffer. It sounds more solid underfoot, transmits less footfall noise and holds up better over the life of the building. We recommend 4.5 kN as the minimum for every office.

Can I put marble or stone on a raised floor?

Yes. nSteelCement is our standard panel and takes marble, stone, porcelain and parquet: fix a plywood, cement board or fibreboard layer to the panels, then lay the finish on it. Carpet tiles, LVT and SPC go straight onto the panel. nGroove is our premium panel for projects that need the hard finish bonded straight to the panel with no board layer.

Can a MEWP or scissor lift be used on a raised access floor?

Yes, on 6.8 kN grades and above. Nord Floors floors at 6.8 kN carry MEWPs on site today. Forklifts and pallet stackers are possible on heavy grades after Nord Floors engineering checks the wheel loads.

When does a raised floor need stringers and mechanical anchoring?

nHPL and nSDV are gravity-laid systems, so they use stringers at every height, from the lowest. nSteelCement and nGroove are corner-locking systems, fixed to the pedestal heads at each corner, so they need stringers only above 600 mm finished floor height. Up to 600 mm, chemical (adhesive) anchoring of the pedestals is enough; above 600 mm, pedestals are mechanically anchored to the slab.

Which standard are Nord Floors raised floors tested to?

Nord Floors follows the CISCA (Ceilings & Interior Systems Construction Association) Recommended Test Procedures for Access Floors for concentrated, ultimate, uniform and rolling loads.

Is woodcore (chipboard) raised flooring suitable for Saudi Arabia?

Usually not the best choice. Woodcore panels have a compressed wood-chip (chipboard) core, made for dry indoor conditions. Coastal humidity in Jeddah and Dammam, water from cleaning or leaks, and wet works during construction can make the core swell and lose strength. Woodcore is combustible (typically Bfl to Dfl fire classes), and many woodcore systems are rated only at light to medium grades. Steel cementitious panels such as nSteelCement are non-combustible (A1), do not swell with moisture, carry 3.7 to 11.1 kN, and last the life of the building; the steel shell is fully recyclable at end of life.

When do I need nHPL or nSDV?

Only where the room needs antistatic (nHPL) or static dissipative (nSDV) flooring, such as data rooms, server rooms and control rooms. Both come with their final finish factory-applied.