nHPL Series
nHPL is a steel cementitious raised access floor panel with a factory-applied antistatic high pressure laminate, made in Dammam. It is for server rooms, data centers and command centers where antistatic flooring is required, with loads from 3.7 to 11.1 kN.
Overview
The same steel cementitious panel as nSteelCement, finished in the factory with antistatic HPL. It is a gravity-laid system on stringers, so any panel lifts out for access to cables and cooling, and drops back into an exact grid.
Features
- Antistatic HPL finish already on the panel.
- Always on stringers for a rigid, gravity-laid grid.
- Same load range as nSteelCement.
- Perforated panels and grilles finished to match.
Illustration. Flat head pedestals.

Being installed. Panels being laid on pedestals and stringers, with cable trays in the void. Illustration.
Specification
| Panel size | 600 × 600 mm |
|---|---|
| Thickness | 35 mm |
| Weight | approx. 13–20 kg |
| Finish | Antistatic high pressure laminate |
| Finished floor height | 80–2000 mm |
| Squareness | 0.75 mm max |
| Flatness | diagonal 1.0 mm, edge 0.6 mm |
| Twist | 1.0 mm |
| Fire | Non-combustible, Class A (ASTM E84), A1 (EN 13501) |
| Acoustic | IIC 58 |
| Pedestal | Flat head, galvanised steel |
Finishes
Factory-applied antistatic high pressure laminate. No site finish needed.
Understructure
Gravity-laid panels on stringers at every height, from the lowest finished floor heights. Chemical anchoring up to 600 mm FFH; mechanical above.
Applications
nHPL load grades
| Grade | Concentrated | Impact | Ultimate | Uniform | Rolling, 10 passes | Rolling, 10,000 passes |
|---|---|---|---|---|---|---|
| HPL370 | 3.7 kN | 0.67 | 10.8 kN | 19.8 kN/م² | 3.0 kN | 2.2 kN |
| HPL450 | 4.5 kN | 0.67 | 13.5 kN | 23.3 kN/م² | 3.6 kN | 3.0 kN |
| HPL560 | 5.6 kN | 0.67 | 16.8 kN | 33.1 kN/م² | 4.5 kN | 3.6 kN |
| HPL680 | 6.8 kN | 0.67 | 20.1 kN | 42.6 kN/م² | 5.6 kN | 4.5 kN |
| HPL890 | 8.9 kN | 0.67 | 26.7 kN | 49.9 kN/م² | 6.7 kN | 5.6 kN |
| HPL1110 | 11.1 kN | 0.67 | 33.3 kN | 58.3 kN/م² | 8.9 kN | 6.7 kN |
Recommended minimum for offices: the 450 grade (4.5 kN). For MEWP access: 680 (6.8 kN) and above. Tested to CISCA Recommended Test Procedures for Access Floors.
Documents
The nHPL data sheet is in Downloads. Ask for the rest with your quotation or submittal pack.
Questions about nHPL
Why does Nord Floors recommend 4.5 kN as a minimum?
Lighter grades can carry ordinary office loads, but a 4.5 kN panel is stiffer. It sounds more solid underfoot, transmits less footfall noise and holds up better over the life of the building. We recommend 4.5 kN as the minimum for every office.
Can I put marble or stone on a raised floor?
Yes. nSteelCement is our standard panel and takes marble, stone, porcelain and parquet: fix a plywood, cement board or fibreboard layer to the panels, then lay the finish on it. Carpet tiles, LVT and SPC go straight onto the panel. nGroove is our premium panel for projects that need the hard finish bonded straight to the panel with no board layer.
Can a MEWP or scissor lift be used on a raised access floor?
Yes, on 6.8 kN grades and above. Nord Floors floors at 6.8 kN carry MEWPs on site today. Forklifts and pallet stackers are possible on heavy grades after Nord Floors engineering checks the wheel loads.
When does a raised floor need stringers and mechanical anchoring?
nHPL and nSDV are gravity-laid systems, so they use stringers at every height, from the lowest. nSteelCement and nGroove are corner-locking systems, fixed to the pedestal heads at each corner, so they need stringers only above 600 mm finished floor height. Up to 600 mm, chemical (adhesive) anchoring of the pedestals is enough; above 600 mm, pedestals are mechanically anchored to the slab.
Which standard are Nord Floors raised floors tested to?
Nord Floors follows the CISCA (Ceilings & Interior Systems Construction Association) Recommended Test Procedures for Access Floors for concentrated, ultimate, uniform and rolling loads.
Is woodcore (chipboard) raised flooring suitable for Saudi Arabia?
Usually not the best choice. Woodcore panels have a compressed wood-chip (chipboard) core, made for dry indoor conditions. Coastal humidity in Jeddah and Dammam, water from cleaning or leaks, and wet works during construction can make the core swell and lose strength. Woodcore is combustible (typically Bfl to Dfl fire classes), and many woodcore systems are rated only at light to medium grades. Steel cementitious panels such as nSteelCement are non-combustible (A1), do not swell with moisture, carry 3.7 to 11.1 kN, and last the life of the building; the steel shell is fully recyclable at end of life.
When do I need nHPL or nSDV?
Only where the room needs antistatic (nHPL) or static dissipative (nSDV) flooring, such as data rooms, server rooms and control rooms. Both come with their final finish factory-applied.
Other Nord Floors series
nSteelCement
Our main seriesSteel cementitious raised access floor for carpet, LVT and SPC, and for marble and stone on a board layer.
View nSteelCement →nGroove
PremiumPremium calcium sulphate raised access floor for hard finishes bonded directly.
View nGroove →nSDV
Static dissipative vinyl raised access floor.
View nSDV →