Raised floors · Glossary
Edge trim
A plastic or metal edge band around a panel that protects the edge, keeps finishes neat and helps panels sit tight in the grid.
Related terms in Raised floors
- Interlocking groove edge
- Panel edges machined with a tongue-and-groove profile so neighbouring panels lock together. It stops panels shifting under rigid finishes such as stone and porcelain.
- Concentrated load
- The load a panel carries on a small area (a 25 × 25 mm indenter in the CISCA test), like a chair leg or cabinet foot, without exceeding the allowed deflection. Nord Floors grades run from 3.7 to 11.1 kN.
- Woodcore panel
- A panel with a particleboard core, usually wrapped in steel or aluminium foil. Lighter and cheaper but more sensitive to humidity and water than steel cementitious or calcium sulphate panels.
- Ultimate load
- The load at which a panel fails in test. Rated loads are set well below it so the floor keeps a wide safety margin.
- Calcium sulphate panel
- A dense, solid panel made from high-density calcium sulphate (often fibre-reinforced). Quiet underfoot and very stiff; nGroove uses it with grooved, interlocking edges for stone and porcelain bonded directly.
- Rolling load
- The load a panel withstands from a wheel rolling across it (pallet trucks, server racks on castors, MEWPs) for a set number of passes, typically 10 and 10,000.
- Steel cementitious panel
- A panel made of a welded steel shell filled with a lightweight cementitious core. Strong, non-combustible and the basis of nSteelCement, nHPL and nSDV.
- Impact load
- The load a panel survives when a weight is dropped onto it, simulating dropped tools and equipment during fit-out.