Louvre selector · MIGUA MIGUSHIELD

Find and size the right louvre

Tell us what the louvre is for, how much air it moves and what it faces: rain, sand or noise. We rank the MIGUSHIELD types, size the opening, check the velocity against water penetration, estimate the pressure drop and write the specification.

1What is the louvre for?

2How much air?

From the mechanical schedule. Leave it at zero if you only need a screen.

Airflow
Height available for the louvre
1200 mm

3Site and exposure

Wind-driven rain

High: coastal storms, exposed facades, intakes that must stay dry.

Sand and dust

Most Saudi sites have normal to high wind-blown sand.

Noise reduction needed
Location

4Finish and accessories

5Recommended MIGUSHIELD louvres

MIGUSHIELD

Sand trap louvre ST4010 Best fit

Vertical channels slow the air so wind-blown sand drops out and drains at the base
92%fit
Size 3100 × 1200 mm · 3 sectionsFace 3.72 m²Free area 1 m² (27%)Core velocity 0.75 m/sFree-area velocity 2.77 m/sPressure drop ≈ 15 PaSand: up to about 90% separation of coarse sand at low face velocity, less for fine dust; add filters for fine dust

Stops wind-blown sand at the intake · Free area from the MIGUSHIELD data sheet; separation and pressure figures typical for the type

Fine dust still passes: add a filter section

MIGUSHIELD

Storm-resistant louvre R7355

Drainable storm-resistant blades for fresh air intakes that must stay dry
66%fit
Size 1550 × 1200 mm · 2 sectionsFace 1.86 m²Free area 0.94 m² (50%)Core velocity 1.49 m/sFree-area velocity 2.97 m/sPressure drop ≈ 37 PaRain class BWater starts at 3.86 m/sDepth 178 mm

Best rain defence for wind-driven rain · AMCA 500-L certified data (Ten Plus R7355)

MIGUSHIELD

Stormproof louvre H6451

Stormproof 45° blades with low pressure drop
62%fit
Size 1900 × 1200 mm · 2 sectionsFace 2.28 m²Free area 1.07 m² (47%)Core velocity 1.22 m/sFree-area velocity 2.59 m/sPressure drop ≈ 10 PaWater starts at 3.32 m/sDepth 152 mm

Good rain defence with less depth · AMCA 500-L certified data (Ten Plus H6451)

MIGUSHIELD

Drainable louvre D6403

Blade gutters and jamb channels drain the water that lands on the blades; best airflow and lowest pressure drop
50%fit
Size 1750 × 1200 mm · 2 sectionsFace 2.1 m²Free area 1.14 m² (55%)Core velocity 1.32 m/sFree-area velocity 2.43 m/sPressure drop ≈ 10 PaWater starts at 4.93 m/sDepth 152 mm

Lowest pressure drop · AMCA 500-L certified data (Ten Plus D6403)

MIGUSHIELD louvres are made by MIGUA with its Canadian partner Ten Plus and certified to AMCA 500-L. Storm-resistant and drainable figures are Ten Plus certified data; acoustic and sand trap figures are typical for the type. The submittal carries the tested data for the chosen model.

© Nordinfini 2026. The logic and data behind this tool belong to Nordinfini. Use it freely for your projects; copying, republishing or automated collection of its results is not permitted. Terms

Questions

How do I size a louvre?

Divide the airflow by the design velocity for the louvre type to get the face area, then fit that area to the height you have. Weather louvres are usually held to about 2.5 m/s (500 fpm) through the free area or less; storm-resistant louvres to the core velocity of their wind-driven rain class, about 1.0 m/s for class A; sand trap and acoustic louvres to about 1.0 m/s face velocity.

What do AMCA 500-L and BS EN 13030 classes mean?

AMCA 500-L gives the free-area velocity at which water starts to come through (the beginning point of water penetration) and the pressure drop. BS EN 13030 rates rain defence from class A (99% effective or better) to D (under 80%) and airflow from class 1 (discharge coefficient 0.4 or more) to class 4 (under 0.2).

Which louvre keeps sand out?

A sand trap louvre such as the MIGUSHIELD ST4010: vertical channels slow the air so sand drops out and drains at the base. It works best at low face velocity, around 1 m/s, and separates coarse sand well; fine dust still needs filters behind it.

Do I need an acoustic louvre for a generator room?

Usually yes when offices, homes or hotel rooms are near. A 150 mm acoustic louvre typically gives around 10 to 12 dB, a 300 mm one around 17 to 19 dB. Large generators often need attenuators as well; we size them with your acoustic consultant.

All about MIGUSHIELD louvres →