Expansion joints & louvres · Glossary

Acoustic louvre

A louvre with deep, sound-absorbing blades that cuts noise from plant and generators. A 150 mm unit typically gives about 10 to 12 dB, a 300 mm unit about 17 to 19 dB.

Related terms in Expansion joints & louvres

Drainable louvre
A louvre whose blades have gutters that carry water to channels in the jambs and down to the sill. Lower pressure drop than storm-resistant blades; best for exhaust and sheltered openings.
Louvered vision screen
A louvre that hides rooftop or yard plant behind a sight barrier while air moves freely. It is not a weather louvre.
Storm-resistant louvre
A louvre with drainable, hooked blades tested against wind-driven rain, for fresh air intakes that must stay dry. Rain classes are given at stated core velocities.
Core velocity
The airflow through a louvre divided by its face (core) area. Rain-defence classes under BS EN 13030 are stated against core velocity.
AMCA 500-L
The laboratory test standard for louvres from the Air Movement and Control Association: pressure drop, water penetration, wind-driven rain and, in recent editions, wind-driven sand.
Free-area velocity
The airflow through a louvre divided by its free area. Water penetration and pressure drop rise with it; about 2.5 m/s (500 fpm) is a common selection limit.
Beginning point of water penetration
In AMCA 500-L, the free-area velocity at which 0.01 oz of water per ft² of free area starts to come through a louvre in a 15-minute test. Select louvres well below it.
Discharge coefficient
A number from BS EN 13030 that rates how easily air passes through a louvre: class 1 is 0.4 or more, class 4 below 0.2. A higher figure means less pressure drop.

All expansion joints & louvres terms → · Full glossary →