Perforated panels and CRAC airflow: how many do you really need?

Too few perforated panels starve the racks; too many waste cold air. Here is how to size them from the cooling units and the IT load, step by step.

Control room on a raised access floor with perforated panels (illustration)

Short answer: add up the air your cooling units can actually deliver into the floor void, take off what leaks out through cable cut-outs and gaps, and divide what is left by the airflow of one perforated panel or grille at your underfloor pressure. Then check the result against the IT load in each row.

Why it matters

In a raised floor data hall, the floor void is the duct. Cold air from CRAC or CRAH units pressurises the void and comes up through perforated panels in front of the racks. If there are too few openings, the pressure is high but the racks at the end of the row go hungry. If there are too many, the pressure collapses and air short-circuits back to the units.

Step 1 — Start from the cooling units

List each unit and its rated airflow. Count only the duty units, not the standby ones — a standby unit should not be needed to keep the room cool.

Step 2 — Allow for leakage

Every cable cut-out without a brush grommet, every gap at a wall and every missing panel lets air escape. A well-sealed floor might lose around 5%; a poorly sealed one can lose a third of the air before it reaches a rack. Fit brush grommets to every cut-out — it is the cheapest cooling upgrade there is.

Step 3 — Choose the opening

  • Perforated panels (about 25% open) suit low to medium densities and give an even, gentle supply.
  • Grilles (higher open area) move much more air per panel and suit high-density rows.
  • Dampers let you trim each opening, at the cost of some airflow.

Step 4 — Divide and check

Divide the available air by the airflow per opening, then check each row: the air delivered to a row should match what the racks in that row draw. Our perforated panel calculator does this for you — enter your units, rows and racks, and it tells you how many panels or grilles to place, and where.

Frequently asked questions

Which raised floor series is best for a data hall? nHPL (antistatic laminate) or nSDV (static dissipative vinyl), on stringers, at a load grade that suits the racks and the equipment used to move them.

Can I move perforated panels later? Yes — that is one of the main advantages of a raised floor. Re-balance as racks are added.

Specify a raised floor in five minutes

Answer a few questions about the room and loads. We’ll recommend the series and grade and work out the airflow.

Open the selector
#data centre#airflow#perforated panel#CRAC